INTRODUCTION
Page 4
1.2 Communication using LAN / Internet
When using LAN / Internet communication between the Dupline-Online Server and the Dupline® Data
Logger the Dupline-Online Server must have a fixed IP address on the network. The reason for this is that
the serial to Ethernet (MOXA NPort) converter must know which IP address to contact when data is to be
exchanged.
The transport of data between the Dupline-Online Server and the Dupline® Data Logger is done with a
TCP/IP socket on a single TCP/IP port. Hence only one TCP/IP port has to be open if there is a firewall
between the Dupline-Online Server and the Dupline® Data Logger. By default TCP/IP port 10100 is used but
the TCP/IP port can be changed in the LogIf service on the Dupline-Online Server.
The TCP/IP socket connection is always opened from the Dupline® Data Logger end. Hence it is always the
Dupline® Data Logger (actually it’s the serial to Ethernet converter) which initiates the TCP/IP socket
connection. The TCP/IP socket is kept alive as long as the Dupline® Data Logger is powered one which
enables control request etc. to be sent from the Dupline-Online Server to the Dupline® Data Logger on the
same TCP/IP socket which is used to send log data from the Dupline® Data Logger to the Dupline-Online
Server.
The fact that the TCP/P socket always is opened from the Dupline® Data Logger end and only one TCP/IP
socket is used for communication in both directions makes the installation and network setup very easy and
straight forward.
The data packages exchanged between the Dupline-Online Server and the Dupline® Data Logger over the
TCP/IP socket are kept at an absolute minimum. When no data is logged only a very small data package is
exchanged every 5 minutes to keep the connection alive. The “keep alive package” is at the same time used
to ensure that the clock in the Dupline® Data Logger is as accurate as possible.